# FAQ: control valves, trim, FIELDVUE, transmitters, Coriolis, quoting Fisher parts

> Technical answers on control valves, repair and trims, FIELDVUE, transmitter selection, Coriolis, ISO/IEC 17025 calibration and how to quote Fisher parts.

Source: https://its-ve.com/en/faq/

---
- [Home](https://its-ve.com/en/)
- Frequently asked technical questions

[Home](https://its-ve.com/en/)

Resources

# Frequently asked technical questions

Short, technical answers. Each one points to the page where the topic is covered in depth.

[Ask a technical question](https://its-ve.com/en/contact/)

## Topics

- Control valves1
- Trims and repair2
- FIELDVUE and diagnostics1
- Measurement and calibration4
- Quoting and spare parts3
- Services and company4

## Control valves

What is a control valve?
A control valve is the final element of a control loop: it changes the passage of a fluid to hold a process variable (flow, pressure, level or temperature) at the value set by the controller. The assembly has three parts: the body, which contains the pressure and carries the fluid; the trim or internals (plug, seat, cage and stem), which governs the opening and defines the flow characteristic; and the actuator, which moves the plug according to the signal received through the positioner. Valves are classified as sliding-stem (globe) and rotary (ball, eccentric disc, butterfly). Selection depends on the fluid, on pressure, temperature and flow, and on severe-service phenomena such as cavitation or noise.

[Read more in: Control valves →](https://its-ve.com/en/products/final-control/control-valves/)

## Trims and repair

When should a control valve be repaired?
A valve is repaired when it no longer performs its function and the damage is in replaceable components. Typical indicators: seat leakage beyond the specified shutoff class, packing leakage, hysteresis or dead band measured in a signature test, slow or erratic actuator response, increasing noise or vibration, and loss of capacity against the nameplate data. The decision requires prior diagnosis: visual and dimensional inspection, stroke test, leak test and, with a digital positioner, online diagnostics. Repair makes sense if the body is sound, the original sizing is still valid and parts are available. If the body is eroded or process conditions have changed, the right answer is to redesign or replace.

[Read more in: Control valve repair →](https://its-ve.com/en/services/control-valve-repair/)

When should the trim be replaced and when can it be restored?
Trim is replaced when it can no longer be recovered within the manufacturer's tolerances or when the process requires a different configuration. Reasons for replacement: wear or erosion beyond the recoverable thickness of the plug, seat or cage; cavitation damage with loss of geometry; material corrosion; and flow changes that leave the original trim wrongly sized. Before replacing, restoration is assessed: if the part keeps its metallurgical condition and its geometry and dimensions allow machining or rebuilding within tolerance, it can be recovered with shorter lead time and lower cost. It is an engineering decision that depends on inspection, measurement, material, loop criticality and availability of the genuine part. Not every trim can be recovered.

[Read more in: Trim restoration →](https://its-ve.com/en/services/trim-restoration/)

## FIELDVUE and diagnostics

What is FIELDVUE?
FIELDVUE is the Fisher (Emerson) family of digital valve controllers. A digital valve controller, or DVC, receives the 4-20 mA or digital control signal (HART, FOUNDATION fieldbus, PROFIBUS), converts it into a pneumatic output to the actuator and also measures position, pressures and temperature to diagnose the condition of the assembly without disassembling it. It replaces analog positioners on most pneumatic actuators. Current models are the DVC6200 and DVC7K; the DVC2000 is the previous generation. Diagnostics are interpreted with ValveLink software, which detects friction, dead band, leaks and instrument-air problems. This makes it possible to plan condition-based maintenance instead of intervening by calendar.

[Read more in: Positioners and instruments →](https://its-ve.com/en/products/final-control/valve-positioners/)

## Measurement and calibration

How do you select a pressure transmitter?
Selection follows an order. First, the pressure type: absolute, gauge or differential. Second, the range: normal operating pressure should sit in the middle of the span, and the process overpressure limits must be checked. Third, the accuracy the loop requires, distinguishing reference accuracy from long-term stability, and whether the figure is stated on span or on reading. Fourth, process contact: wetted-parts material and the need for a remote seal on corrosive, viscous or hot fluids. Fifth, the process connection and accessories (manifold). Sixth, the output signal (4-20 mA HART, fieldbus, wireless), hazardous-area approvals and the periodic calibration plan.

[Read more in: Pressure measurement →](https://its-ve.com/en/products/measurement/pressure/)

How often should a transmitter be calibrated?
There is no single interval. The user sets it based on the manufacturer's recommendation, loop criticality, the accuracy the process requires, installation conditions (vibration, ambient temperature, fluid) and contractual or regulatory requirements such as custody transfer. Sound practice is to record the as-found result at every calibration: if the instrument is repeatedly within tolerance, the interval can be extended; if it is found out of tolerance, the interval should be shortened and the cause investigated. Transmitters with built-in diagnostics help detect drift between calibrations, but they do not replace comparison against a traceable standard.

[Read more in: Calibration →](https://its-ve.com/en/services/calibration/)

What is ISO/IEC 17025?
It is the international standard that sets the requirements for the competence, impartiality and consistent operation of testing and calibration laboratories. A laboratory accredited under ISO/IEC 17025 has shown an accreditation body that its methods are validated, its standards are traceable and its staff are competent for a defined scope; accreditation covers only the quantities and ranges in that scope. ITS provides its calibration service for pressure, temperature, flow and volume instruments certified under ISO/IEC 17025:2017.

[Read more in: Calibration →](https://its-ve.com/en/services/calibration/)

Coriolis vs. other flow measurement technologies?
A Coriolis meter measures mass flow directly from the vibration of its tubes and also delivers density and temperature; it does not depend on pressure, temperature or flow profile and is the most accurate technology, which is why it is used for custody transfer and batching. A magnetic meter measures volume and only works with conductive liquids: economical and unobstructed, but useless for hydrocarbons. An ultrasonic meter measures velocity, allows non-intrusive installation and large diameters, with lower accuracy in demanding services. A turbine meter measures volume with good accuracy on clean liquids, but has moving parts and needs frequent recalibration. Coriolis costs more and limits line size; its calibration requires a laboratory with an accredited scope.

[Read more in: Flow measurement →](https://its-ve.com/en/products/measurement/flow/)

## Quoting and spare parts

What information is needed to quote a valve?
For a complete valve: fluid and its state (liquid, gas, steam, two-phase), minimum, normal and maximum flow, inlet and outlet pressures, temperature, density or molecular weight, viscosity, line size and pressure class, required materials, end connection, available control signal, instrument air and fail action (open or close). For a spare part: serial number and type from the nameplate, size and class, body and trim material, part number if known, quantity and required lead time. In both cases a photo of the nameplate, the instrument tag and a description of the symptom help. The serial number recovers the original factory configuration.

[Read more in: Request a quote →](https://its-ve.com/en/request-a-quote/)

How do you identify Fisher parts?
Identification starts from the body and actuator nameplates. They show serial number, type or model (ET, ED, EZ, GX, V150), size, pressure class, materials and often trim type and flow characteristic. The serial number gives access to the manufacturing record, which states the original configuration and the exact part numbers; it is the safest method. If the nameplate is illegible, use the parts list in the model's instruction manual and measure the part (seat diameter, travel, material). Genuine parts keep the dimensions and materials of the original design; imitation parts can alter control and service life.

[Read more in: Fisher OEM parts →](https://its-ve.com/en/products/final-control/fisher-oem-parts/)

Do you hold inventory in Venezuela?
ITS works with inventory in Puerto Ordaz and with the inventory and logistics of its parent company, ACD America Corp., in Orlando. Availability of each part or unit is checked on every request: the answer states where the material is, the lead time and the price. To check it, send the part number or model with the required quantity; if the part is not in Venezuela, supply from Orlando is quoted. The site does not publish fixed stock levels because they change daily.

[Read more in: Inventory →](https://its-ve.com/en/inventory/)

## Services and company

How often should pressure safety valves (PSV) be tested?
The interval is set by the plant's inspection program, not by a fixed figure. It is defined by the regulations and codes that apply to the installation, recommended practices for inspecting pressure-relieving devices (such as API RP 576), service severity (corrosive, dirty or polymerizing fluids), the as-received test history and the criticality of the protected equipment. If a PSV is repeatedly found within its set pressure and leak-tight, the interval can be extended on a risk basis; if it fails, the interval is shortened. Each test should record opening pressure, seat tightness and the condition of the internals.

[Read more in: Regulators and relief →](https://its-ve.com/en/services/regulators-and-relief/)

Do you repair valves on site or only in the workshop?
Both. The workshop handles repairs that require complete disassembly, replacement of internals and bench leak and stroke tests, with a report. On site, field service covers diagnostics, positioner adjustment and calibration, packing replacement, commissioning and turnaround support, as long as safety conditions and equipment isolation allow it. The decision depends on the scope of the failure, the downtime available and whether the valve can be taken out of line.

[Read more in: Field service →](https://its-ve.com/en/services/field-service/)

What is the relationship between ITS and Emerson and its brands?
ITS de Venezuela is an independent company. It supplies products and spare parts from Emerson brands (Fisher, Rosemount, Micro Motion, Crosby, Bettis and Hytork, among others) and provides technical service on that equipment, but it is not the manufacturer. The brands belong to Emerson Electric Co. For factory technical documentation, the ITS library points to the current official source instead of republishing it. Its parent company is ACD America Corp., in Orlando (Florida).

[Read more in: Brands →](https://its-ve.com/en/brands/)

Do you deliver In-Company courses?
Yes. The ITS Training Division delivers its programs at the client's facilities, using the plant's own equipment and cases, so operations do not stop and staff do not travel. Programs include course 1300 on control valve engineering (selection and sizing), course 1400 for control valve technicians (installation, calibration and maintenance), and the ValveLink and instrumentation and control courses. Content is adapted to the group's level and to the installed equipment; downloadable syllabi are in the technical library.

[Read more in: Training →](https://its-ve.com/en/services/training/)

## Your question is not here?

Write to us with the model, the symptom or the application and a specialist will answer.

[Ask a technical question](https://its-ve.com/en/contact/) [Message on WhatsApp](https://wa.me/14074625160?text=Hello%20ITS%2C%20I%20would%20like%20to%20talk%20to%20a%20specialist.)