# Fisher 119EZ and 119EZS fuel gas valves for burners

> Fisher 119, 119EZ and 119EZS fuel gas valves for natural-draft burners in oil and gas, with tunable opening speed. Quotations, parts and service.

Source: https://its-ve.com/en/products/final-control/regulators/fuel-gas-valves/

---
- [Home](https://its-ve.com/en/)
- [Products](https://its-ve.com/en/products/)
- [Final control](https://its-ve.com/en/products/final-control/)
- [Regulators](https://its-ve.com/en/products/final-control/regulators/)
- Fuel gas valves

[Regulators](https://its-ve.com/en/products/final-control/regulators/)

Regulators · Fisher

# Fisher 119, 119EZ and 119EZS fuel gas valves

The valve that admits gas to the main burner on fired production equipment: compact, low-leakage and with tunable opening for stable ignition.

[Quote fuel gas valves](https://its-ve.com/en/request-a-quote/?modelo=Fisher%20119EZ%20fuel%20gas%20valve) [Regulators](https://its-ve.com/en/products/final-control/regulators/)

- Overview
- Models
- How it works
- Applications
- ITS
- Resources
- FAQ

## What is a fuel gas valve for burners?

The fuel gas valve carries out the burner management system command on fired heaters, treaters and reboilers: it is a normally closed diaphragm valve that opens on control pressure and closes by spring when it is lost.

The Fisher Types 119EZ and 119EZS serve oil and gas natural-draft burners. Their speed controller tunes the opening to help ensure ignition of the main burner, and the 119EZS adds a solenoid valve for automated systems.

- For natural-draft burners
- Built-in opening speed controller
- 119EZS with solenoid valve
- Low leakage and simple spring adjustment

Models

## Fisher fuel gas models

Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.

Fisher

119EZ

### Fisher Type 119EZ fuel gas valve

For natural-draft burners, with a built-in speed controller to tune opening.

[View bulletin](https://www.emerson.com/is/content/emerson/en/final-control/flow-controls/documents/data-sheets-119-series-fuel-gas-valve-bulletin-fisher-en.pdf) [Fuel gas valves](https://its-ve.com/en/products/final-control/regulators/fuel-gas-valves/) [View sheet](https://its-ve.com/en/products/final-control/regulators/119ez/)

Fisher

119EZS

### Fisher Type 119EZS fuel gas valve

Variant with solenoid valve for automated burner systems.

[View bulletin](https://www.emerson.com/is/content/emerson/en/final-control/flow-controls/documents/data-sheets-119-series-fuel-gas-valve-bulletin-fisher-en.pdf) [Fuel gas valves](https://its-ve.com/en/products/final-control/regulators/fuel-gas-valves/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Fisher%20119EZS)

Fisher

119

### Fisher Type 119 switching valve

On-off or throttling control of noncorrosive or mildly corrosive gases at low pressure.

[View bulletin](https://www.emerson.com/is/content/emerson/en/final-control/flow-controls/documents/data-sheets-119-series-fuel-gas-valve-bulletin-fisher-en.pdf) [Fuel gas valves](https://its-ve.com/en/products/final-control/regulators/fuel-gas-valves/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Fisher%20119)

Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.

How it works

## How it works

A spring holds the disk against the orifice and the valve closed. When the temperature controller or burner management system applies pressure on the diaphragm, it overcomes the spring and opens the gas passage. When the signal is removed, the spring closes the valve: the failure position is closed, as a fuel gas train requires.

On a natural-draft burner, abrupt opening can blow out the pilot or cause a violent light-off; opening that is too slow delays ignition. The built-in speed controller of the 119EZ regulates the opening rate so that gas arrives progressively and the main burner lights from the pilot.

### Constructions and trim

- #### Type 119EZ Fuel gas valve with built-in speed controller, on the compact Type 119 platform.
- #### Type 119EZS The 119EZ with a solenoid valve, for burner management systems with electrical control.
- #### Type 119 Switching valve for on-off or throttling control in low-pressure gas applications.
- #### Common internals Diaphragm, disk, orifice and springs shared between the 119 and the 119EZ, which reduces the spare parts inventory.

Applications

## Where they are used

- Natural-draft burners on line heaters and indirect heaters
- Heater treaters, heated separators and production dehydrators
- Glycol and amine reboilers in gas plants
- Fuel gas trains of tank heaters and fired equipment
- Low-pressure gas switching with the Type 119

### Why it is chosen

- Tunable opening speed for proper ignition of the main burner
- Quick and easy leak detection, according to the manufacturer
- Simple spring adjustment and low leakage
- Compact platform with internals common across models

### Worth weighing

- It is the main burner valve, not the pressure regulator of the train: a pressure reducing regulator is installed upstream to set gas pressure
- It is intended for noncorrosive or mildly corrosive gases; with sour or wet gas, materials are reviewed before selection

ITS de Venezuela

## What ITS does with fuel gas valves

ITS quotes new Fisher 119, 119EZ and 119EZS valves and their genuine parts (diaphragms, disks, orifices and springs), and services installed fuel gas trains: field checks and adjustment, soft parts replacement and leak testing in the Puerto Ordaz workshop, with the support of the Venezuela ↔ Orlando inventory. To get a quotation, send this data: gas and its condition, inlet pressure, flow or burner duty, connection size and type, control signal pressure and whether the system uses a solenoid; or the nameplate model if it is a replacement.

[Quote parts or repair](https://its-ve.com/en/request-a-quote/?modelo=Fisher%20119EZ%20fuel%20gas%20valve)
- ### Regulators and relief Maintenance of pressure regulators and relief devices.
- ### Field service On-site support, shutdowns, commissioning and start-up.
- ### Inventory management Critical spares identified and available before the shutdown.

Resources

## Resources

The full category, the technical library and the manufacturer’s official documentation.

- Category ### Regulators Pressure-reducing, backpressure, fuel gas and slam-shut.
- Technical library ### Manuals, bulletins and selection guides Our own documents and official Fisher links for each family.
- Manufacturer ### Official Fisher catalog (opens in a new tab) Product pages, bulletins and manuals on emerson.com.

FAQ

## Frequently asked questions

[All frequently asked questions](https://its-ve.com/en/faq/)
Why does opening speed matter on a natural-draft burner?
Because combustion air enters only through the stack draft. If gas arrives all at once, the mixture can blow out the pilot or light with a pressure surge in the firebox; if it arrives too slowly, ignition is delayed. The speed controller of the 119EZ allows that rate to be tuned on site until ignition is stable.

What is the difference between the 119EZ and the 119EZS?
The 119EZS includes a solenoid valve, so the burner management system can command it with an electrical signal. The 119EZ is actuated by control pressure from a pneumatic controller. The body and internals belong to the same platform.

Regulators

## More regulators families

### Pressure reducing regulators

They hold downstream pressure constant with a diaphragm and a spring: the simple, fast solution for steam, water, air, gases and chemicals.

### Pilot-operated regulators for natural gas

A pilot amplifies every slight change in outlet pressure and drives the main valve: more capacity and pressure closer to set point than direct operation.

### Back pressure regulators and relief

They control upstream pressure: they stay closed up to set point and pass only the excess to the return line, another pressure level or the vent.

### Slam-shut devices

They shut off the gas supply quickly and completely when pressure leaves the set limits, and stay closed until manually reset.

### Steam regulators

They reduce steam pressure from the distribution lines to the level each consumer needs, on wet or dry steam and without instrument air.

Trademark notice

Emerson, Fisher, FIELDVUE, ValveLink, Rosemount, Micro Motion, Crosby, Bettis and Hytork are registered trademarks owned by Emerson Electric Co. or its affiliates. ITS de Venezuela C.A. supplies products and provides services independently and does not claim to be the manufacturer or an authorized representative of these brands except where expressly stated with supporting documentation.

## Need fuel gas valves, or repair for yours?

Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.

[Quote fuel gas valves](https://its-ve.com/en/request-a-quote/?modelo=Fisher%20119EZ%20fuel%20gas%20valve) [Regulators and relief](https://its-ve.com/en/services/regulators-and-relief/)