# Rosemount 8800 and 8600 vortex flow meters for steam, gas and liquids

> Rosemount 8800 and 8600 vortex flow meters for steam, gases and liquids: no moving parts and no impulse lines. MultiVariable, Dual and Quad versions.

Source: https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/

---
- [Home](https://its-ve.com/en/)
- [Products](https://its-ve.com/en/products/)
- [Measurement](https://its-ve.com/en/products/measurement/)
- [Flow](https://its-ve.com/en/products/measurement/flow/)
- Vortex flow meters

[Flow](https://its-ve.com/en/products/measurement/flow/)

Flow · Rosemount

# Rosemount 8800 vortex flow meters

It measures by counting vortices: a rugged technology for steam and general services, with redundant versions for safety loops.

[Quote vortex flow meters](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20vortex%20flow%20meter) [Flow](https://its-ve.com/en/products/measurement/flow/)

- Overview
- Models
- How it works
- Applications
- ITS
- Resources
- FAQ

## What is a vortex flow meter?

A vortex meter measures the volume flow of liquids, gases and steam with the same device, because its principle does not depend on the state of the fluid. Pressure and temperature are added for mass flow; the MultiVariable version of the Rosemount 8800 integrates temperature.

It uses the von Kármán effect: the shedder bar sheds alternating vortices whose frequency is proportional to velocity. The 8800 has no gaskets or ports to clog; the 8600 covers general-purpose and utility duty.

- Liquids, gases and steam
- No moving parts
- No impulse lines, no zeroing
- Redundant Dual and Quad versions

Models

## Rosemount vortex flow meter models

Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.

Fisher

8800 Flanged

### Rosemount 8800 flanged vortex flow meter

Gasket-free, non-clog meter body: eliminates potential leak points.

[Vortex flow meters](https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20Flanged)

Fisher

8800 Wafer

### Rosemount 8800 wafer vortex flow meter

Lightweight and cost-effective, easy to install in utility services.

[Vortex flow meters](https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20Wafer)

Fisher

8800 Reducer

### Rosemount 8800 reducer vortex flow meter

Integral reducers to measure lower flow rates with the same electronics and sensor.

[Vortex flow meters](https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20Reducer)

Fisher

8800 Dual

### Rosemount 8800 Dual vortex flow meter

Redundant measurement with one-out-of-two or two-out-of-two voting against false trips.

[Vortex flow meters](https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20Dual)

Fisher

8800 Quad

### Rosemount 8800 Quad vortex flow meter

Two-out-of-three voting plus a fourth integrated transmitter for process control.

[Vortex flow meters](https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20Quad)

Fisher

8600

### Rosemount 8600 vortex flow meter

For general-purpose and utility duty: clean fluids and steam.

[Vortex flow meters](https://its-ve.com/en/products/measurement/flow/vortex-flow-meters/) [Quote this model](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208600)

Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.

How it works

## How it works

The vortices make a sensing element oscillate at a frequency the transmitter counts and converts into velocity. There are no moving parts to wear and no impulse lines to plug, and the meter needs no zeroing. Electronics and sensor are verified internally.

Accuracy depends on the installation: enough straight run, correct mounting and a meter sized for the actual flow. At low flow rates, a body with integral reducers keeps velocity within the measurable range without changing the piping.

### Constructions and trim

- #### Flanged and wafer The flanged 8800 is the process configuration; the lighter wafer mounts between flanges in utility services.
- #### With integral reducers The 8800 Reducer uses the same electronics, sensor and meter body of the series, with a built-in reduction for low flow rates.
- #### MultiVariable Combines flow and temperature in a single instrument, with the temperature measurement isolated from the process and separate from the vortex sensor.
- #### Dual and Quad Several transmitters on one meter body for redundant measurement with voting, suitable for safety instrumented systems.

Applications

## Where they are used

- Saturated and superheated steam: distribution, consumption and energy balances
- Process gases and compressed air
- Clean, low-viscosity liquids in general and utility services
- Safety loops that require redundant flow measurement
- Chemical, power generation and water treatment

### Why it is chosen

- A single technology for liquids, gases and steam
- No moving parts and no impulse lines: less maintenance and fewer leak points
- Good vibration immunity and internal verification of electronics and sensor
- Redundant configurations on a single body to avoid false trips

### Worth weighing

- It needs a minimum velocity to shed vortices: it does not measure very low flows and must be sized for the actual flow
- It requires straight run and correct mounting; external vibration and fluid properties affect accuracy

ITS de Venezuela

## What ITS does with vortex flow meters

We quote new Rosemount vortex meters and their accessories, configure and commission the meter in the field, calibrate it through our calibration service, in the field and in the laboratory, and integrate it into the control loop. We reply with availability in Venezuela or Orlando. To quote, send the fluid and its state (liquid, gas or steam), flow range, operating pressure and temperature, line size, connection and output signal.

[Quote parts or repair](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20vortex%20flow%20meter)
- ### Calibration Pressure, temperature, flow and volume, in the field and in the laboratory.
- ### Field service On-site support, shutdowns, commissioning and start-up.
- ### Automation and control Loops, actuation, re-engineering and equipment upgrades.

Resources

## Resources

The full category, the technical library and the manufacturer’s official documentation.

- Category ### Flow Coriolis, magnetic, vortex and differential pressure.
- Technical library ### Manuals, bulletins and selection guides Our own documents and official Fisher links for each family.
- Manufacturer ### Official Rosemount catalog (opens in a new tab) Product pages, bulletins and manuals on emerson.com.

FAQ

## Frequently asked questions

[All frequently asked questions](https://its-ve.com/en/faq/)
Does a vortex meter measure steam mass flow?
The principle measures velocity, that is, volume. Mass is obtained by compensating with pressure and temperature. The 8800 MultiVariable integrates the temperature measurement in the same instrument, which avoids installing two or more separate devices.

What are the Dual and Quad versions for?
Redundancy. The 8800 Dual protects against false trips with one-out-of-two or two-out-of-two voting; the 8800 Quad uses two-out-of-three voting and includes a fourth integrated transmitter for process control.

Flow

## More flow families

### Coriolis flow meters

Direct mass flow, with density and temperature from the same device, for liquids, gases and slurries.

### Magnetic flow meters

Volume flow in conductive liquids and slurries, with a full bore and no moving parts.

### Differential pressure flow

Annubar, compact and integral orifice, and orifice plates: standardized measurement for gas, liquid and steam.

### Density and viscosity

Density, concentration, specific gravity and viscosity measured in line, in real time.

Trademark notice

Emerson, Fisher, FIELDVUE, ValveLink, Rosemount, Micro Motion, Crosby, Bettis and Hytork are registered trademarks owned by Emerson Electric Co. or its affiliates. ITS de Venezuela C.A. supplies products and provides services independently and does not claim to be the manufacturer or an authorized representative of these brands except where expressly stated with supporting documentation.

## Need vortex flow meters, or calibration for yours?

Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.

[Quote vortex flow meters](https://its-ve.com/en/request-a-quote/?modelo=Rosemount%208800%20vortex%20flow%20meter) [Calibration](https://its-ve.com/en/services/calibration/)