Fisher FIELDVUE digital valve controller mounted on a control valve actuator

Positioners and instruments · Fisher

Fisher FIELDVUE digital valve controllers

A positioner with a microprocessor: it takes the valve to set point, communicates over HART or fieldbus and monitors the state of the assembly online.

What is a digital valve controller?

A digital valve controller is a microprocessor-based instrument that receives the set point from the control system, compares it with the actual stem or shaft position and delivers to the actuator the air pressure needed to make the two match.

Besides positioning, it enables diagnostics and two-way communication over HART, FOUNDATION fieldbus and PROFIBUS. In the Fisher FIELDVUE family, the DVC7K and DVC6200 serve control valves; the DVC6200 SIS serves safety instrumented systems.

Fisher FIELDVUE digital valve controller mounted on a control valve actuator
  • Microprocessor-based instrument
  • HART, FOUNDATION fieldbus and PROFIBUS
  • Linkage-less, non-contact feedback
  • Online diagnostics with ValveLink

Models

FIELDVUE models

Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.

Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.

How it works

How it works

The instrument converts the input signal into a pneumatic output to the actuator and closes the loop by measuring travel. On FIELDVUE instruments that feedback is linkage-less: a system with no physical contact that eliminates wear on parts. The electronics, encapsulated or conformal coated depending on the model, resist the effects of vibration, temperature and corrosive atmospheres.

Besides positioning, the controller diagnoses itself and evaluates valve performance and health. With ValveLink software, tests are run on the entire control valve assembly, which helps pinpoint problems without disrupting the process and before the equipment fails. The modular design allows critical working components to be replaced without removing field wiring or pneumatic tubing.

Constructions and trim

  • FIELDVUE DVC7K

    On-board analytics (Advice at the Device), local user interface, NE 107 LED health indicator and Bluetooth technology to see health across multiple valves.

  • FIELDVUE DVC6200

    A HART communicating instrument: information can be accessed anywhere along the loop, which reduces personnel exposure in hazardous or hard-to-reach locations.

  • FIELDVUE DVC6200 SIS

    Controls the valve safety shutdown function and, with partial stroke testing, allows the time between proof tests to be extended without taking the valve offline.

  • FIELDVUE DVC2000

    Compact, with a multilingual liquid crystal display and a local interface; integral mounting is available on the Fisher GX and on 657 and 667 size i actuators.

Applications

Where they are used

  • Control valves in modulating service that must run close to set point
  • Replacement of pneumatic and analog positioners on installed valves
  • Safety instrumented system shutdown valves, with partial stroke testing
  • Critical valves where condition-based maintenance planning matters
  • Valves in hazardous or hard-to-reach locations, evaluated remotely

Why it is chosen

  • Quick response to large step changes and precise control for small set point changes
  • Non-contact feedback: no linkage to wear
  • Self-diagnostics that evaluate valve performance and health without shutting down the process
  • Modular design: critical components are replaced without removing wiring or tubing

Worth weighing

  • Making use of the diagnostics requires the software, the right diagnostic level in the instrument and personnel trained to interpret the results
  • The communication protocol, the mounting on the actuator and the area classification must be defined when the instrument is specified

ITS de Venezuela

What ITS does with FIELDVUE controllers

We quote new FIELDVUE controllers, mounting kits and genuine parts, install them on the actuator and commission them: configuration, travel calibration and tuning. With ValveLink we obtain the valve signature and the diagnostics of the assembly, in our Puerto Ordaz workshop or in the field, and we train the personnel who will interpret the results. Parts are managed through the Venezuela ↔ Orlando inventory. For a quotation, send the actuator model and size, the valve type, the communication protocol, the area classification and, if it is a replacement, the installed positioner.

Quote parts or repair

Resources

Resources

The full category, the technical library and the manufacturer’s official documentation.

FAQ

Frequently asked questions

All frequently asked questions
How does a digital valve controller differ from a positioner?

A positioner serves a single purpose: keeping the valve at the position the set point calls for. A digital valve controller does the same and, thanks to its microprocessor, adds diagnostics and two-way communication over protocols such as HART, FOUNDATION fieldbus and PROFIBUS, which simplifies setup and troubleshooting.

Can an analog positioner be replaced with a FIELDVUE instrument?

On most pneumatic actuators, yes. The change requires the right mounting kit for the actuator, configuration of the instrument and travel calibration. ITS evaluates the mounting before quoting.

Positioners and instruments

More positioners and instruments families

Pneumatic positioners

They deliver air to the actuator until stem or shaft position matches the set point, with a pneumatic or 4-20 mA signal.

Process controllers

They close the loop in the field: they measure the variable, compare it with the set point and send the corrective signal to the final element.

Level controllers

They measure and control liquid level, the interface between two liquids or density with a displacer sensor, in pneumatic, electric or digital versions.

I/P transducers

They convert the 4-20 mA electrical signal into a proportional pneumatic pressure: the link between the electronic loop and the air-operated valve.

Volume boosters and accessories

The accessories that complete the assembly: they speed up the stroke, report position, condition the air and define what the valve does if supply fails.

Fisher OEM Parts is the online catalog of ACD America Corp., our parent company. It opens in a new tab.

Need digital valve controllers, or repair for yours?

Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.