Fisher
X-well
Rosemount X-well technology
Measures process temperature with no thermowell and no pipe penetration.
Temperature · Rosemount
A new temperature point without stopping the plant: it clamps to the pipe, calculates process temperature and sends it by radio.
It means measuring process temperature without inserting anything into the process. With Rosemount X-well technology, a pipe clamp sensor measures at the pipe surface and the transmitter calculates the temperature of the fluid.
With no thermowell there is no calculation, weld, flange, potential leak point or shutdown to install it. The family adds the Rosemount 648 and 848T wireless transmitters, with WirelessHART, and the Synchros monitor for assets that were not measured before.
Models
Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.
Fisher
X-well
Measures process temperature with no thermowell and no pipe penetration.
Fisher
648 Wireless
Transmitter with the WirelessHART protocol for points without wiring.
Fisher
848T
Several sensor inputs in a single wireless device.
Fisher
Synchros
Wireless device that measures surface or ambient temperature to watch over assets.
Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.
How it works
The 0085 pipe clamp sensor is fixed to the pipe and measures its surface temperature. The transmitter also measures ambient temperature and, with the pipe properties entered in the configuration, applies an algorithm that calculates the process temperature inside.
In the wireless version, the transmitter runs on a power module and joins a WirelessHART network; the gateway delivers the data to the control or monitoring system. The assembly is installed and removed without disturbing the process.
Non-intrusive measurement technology: a surface sensor plus calculation of process temperature in the transmitter.
Fixed to the pipe with a clamp. It is the sensor for X-well solutions and for surface measurements.
The 648 serves one point; the 848T groups several sensors. Both communicate over WirelessHART.
A wireless surface temperature device to monitor asset condition, with the Plantweb Insight application.
Applications
ITS de Venezuela
We quote new Rosemount X-well solutions, pipe clamp sensors, wireless transmitters, gateways and power modules; we install, configure and commission them in the field, calibrate the transmitters and sensors through our calibration service, in the field and in the laboratory, and integrate the data into the control or monitoring system. We reply with availability in Venezuela or Orlando. To quote, send the fluid and its temperature range, pipe diameter, material and schedule, whether it is insulated, the number and location of points and the system the data must reach.
Quote parts or repairPressure, temperature, flow and volume, in the field and in the laboratory.
On-site support, shutdowns, commissioning and start-up.
Loops, actuation, re-engineering and equipment upgrades.
Resources
The full category, the technical library and the manufacturer’s official documentation.
Category
Transmitters, RTD and thermocouple sensors, thermowells.
Technical library
Our own documents and official Fisher links for each family.
Manufacturer
Product pages, bulletins and manuals on emerson.com.
A pipe clamp sensor measures the surface temperature of the pipe and the transmitter calculates the process temperature from that reading, the ambient temperature and the pipe properties. It needs no thermowell and no process penetration.
To know its condition without touching it. The general temperature of an asset reveals incipient problems, for example in reciprocating compressor valves, rotating equipment or steam-traced lines, and allows action before failure.
Temperature

They convert RTD and thermocouple signals into 4-20 mA, HART, fieldbus or wireless, and watch over sensor health.

Platinum RTDs for accuracy and stability; thermocouples for high temperature, vibration and fast response.

The well that protects the sensor from the process and lets it be removed without stopping the line, calculated against vibration.
Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.