Pressure instruments installed on a fuel gas skid

Pressure · Rosemount

Rosemount pressure transmitters

The most repeated instrument in the plant: it measures pressure and, through it, flow and level.

What is a pressure transmitter?

A pressure transmitter measures process pressure and converts it into an electrical signal, analog or digital, for the control system. The Rosemount line runs from the compact 2088 and the general-purpose 2051 to the 3051, the 3051S and the 4051S.

It is chosen by measurement type: gauge, referenced to atmosphere and the most common; absolute, referenced to a perfect vacuum; or differential, which also lets you infer flow and level. Multivariable models measure more than one at once.

Pressure instruments installed on a fuel gas skid
  • Gauge, absolute and differential
  • Coplanar or in-line mounting
  • 4-20 mA HART, fieldbus and wireless
  • Multivariable versions

Models

Rosemount pressure transmitter models

Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.

Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.

How it works

How it works

Process pressure acts on an isolating diaphragm and reaches the sensor, whose signal the electronics linearize, compensate for temperature and convert into the output. Configuration, ranging and diagnostics are done from the local display, a communicator or the asset management system.

Mounting defines the installation. On the Coplanar platform the sensor module couples directly to the manifold, which allows compact differential pressure, flow and level assemblies. In-line transmitters thread onto the tap for gauge or absolute pressure.

Constructions and trim

  • Coplanar

    The sensor module mounts directly on the manifold. It is the basis of the differential pressure, flow and level configurations of the 3051, 3051S and 2051 series.

  • In-line

    Direct threaded process connection for gauge and absolute pressure, as in the 2088 and the in-line versions of the 3051 and 2051.

  • Multivariable

    Measures differential pressure, static pressure and process temperature, and calculates compensated mass flow in the transmitter itself.

  • Outputs and protocols

    For the 3051 the manufacturer publishes 4-20 mA HART, WirelessHART, FOUNDATION Fieldbus, PROFIBUS and 1-5 V low-power HART outputs.

Applications

Where they are used

  • Pressure in lines, vessels, headers and pump and compressor discharges
  • Flow by differential pressure with an orifice plate or Annubar
  • Level in open and pressurized tanks by hydrostatic head
  • Pressure drop across filters, exchangers and beds
  • Control and protection loops that require diagnostics of the installation

Why it is chosen

  • One platform for pressure, flow and level: fewer models to maintain
  • Diagnostics that detect plugged impulse lines and loop problems
  • A range of protocols, wetted materials and hazardous-area approvals
  • Factory-assembled with manifold, seal or primary element

Worth weighing

  • The transmitter should work in the middle of its range: oversizing it costs accuracy at the low end
  • Impulse lines are the weak point of the installation: plugging, leaks and freezing affect the reading

ITS de Venezuela

What ITS does with pressure transmitters

We quote new Rosemount transmitters with their manifolds, seals and accessories, configure and commission them in the field, calibrate them through our calibration service, in the field and in the laboratory, and integrate them into the control loop. We reply with availability in Venezuela or Orlando. To quote, send the pressure type, range, fluid and its temperature, process connection, output signal and required approvals, or the nameplate model code if it is a replacement.

Quote parts or repair
  • Calibration

    Pressure, temperature, flow and volume, in the field and in the laboratory.

  • Field service

    On-site support, shutdowns, commissioning and start-up.

  • Automation and control

    Loops, actuation, re-engineering and equipment upgrades.

Resources

Resources

The full category, the technical library and the manufacturer’s official documentation.

FAQ

Frequently asked questions

All frequently asked questions
Coplanar or in-line mounting?

Coplanar couples the sensor module directly to the manifold and is the choice for differential pressure, flow and level. In-line mounting threads onto a single tap and is the usual option for gauge and absolute pressure.

What sets the 3051S apart from the 3051?

The 3051S is the scalable Rosemount platform: the multivariable, electronic remote sensor and level versions are built on its sensor module. The 3051 is the most widely used transmitter and the one with the most communication protocols. The choice depends on the accuracy and diagnostics the loop needs.

Pressure

More pressure families

Wireless pressure

Transmitters and gauges with WirelessHART for the points where running cable is not justified.

Manifolds

Isolation, equalization and venting of the transmitter in one compact block, assembled and tested with it.

Diaphragm seals

Remote seals and electronic remote sensors to measure where the transmitter cannot touch the fluid.

Need pressure transmitters, or calibration for yours?

Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.

Product bulletin

Loading the bulletin…

  1. 1Details
  2. 2Verification
  3. 3Request

Message us on WhatsApp

We verify your details and connect you with the specialist for your region.

Receive the phone code by

We will send one code to your email and another to your phone.