Fisher
OSE
Fisher Type OSE slam-shut valve
Totally and rapidly cuts gas flow on overpressure or underpressure; top entry for in-line maintenance.
View bulletin
Regulators · Fisher
Overpressure protection by containment: instead of venting gas, the device closes the line and keeps it closed until someone corrects the cause and resets it.
A slam-shut valve, or safety shutoff valve, rapidly and totally shuts off gas flow in case of failure, to prevent exceeding the maximum allowable operating pressure downstream of the regulator.
It protects by containment: it closes the line instead of discharging to atmosphere, and most trip on both overpressure and underpressure. It comes standalone, such as the Fisher OSE and VS100, or integrated in regulators of the EZR, EZH, 627 and 299H series.
Models
Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.
Fisher
OSE
Totally and rapidly cuts gas flow on overpressure or underpressure; top entry for in-line maintenance.
View bulletin
Fisher
VS100
Family that shuts off on high or low outlet pressure: VS110 with the VSX4 device and VS120 with the VSX8.
View bulletin
Fisher
EZROSX
EZR pilot-operated regulator with integrated slam-shut device, for overpressure, underpressure or both.
View bulletin
Fisher
299HV
Pilot-operated regulator of the 299H Series for applications where the gas supply must be shut off.
View bulletinBrand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.
How it works
A trip mechanism senses downstream pressure through an impulse line and compares it with two springs, one for maximum and one for minimum. While pressure is inside the window, a latch holds the plug open against a closing spring. When pressure leaves the limits, the latch releases and the plug slams shut on its seat.
After tripping, the valve does not reopen on its own. For the OSE, the manufacturer states that it stays closed until the system is shut down and the valve is manually reset, and that an O-ring on the plug provides tight shutoff. Its two-stage tripping mechanism reduces nuisance trips caused by vibration or inlet pressure variations.
Top entry for maintenance without removing the body from the line, accuracy up to ±1% regardless of inlet pressure and flow rate, and an optional limit switch for remote alarm.
VS110 with the VSX4 device and VS120 with the VSX8. Modular body that allows a regulator module to be added later without piping changes.
The shutoff device is mounted on the regulator itself, as on the EZROSX or the 299HV: regulation and protection by containment in a single unit.
The springs of the mechanism define the trip points; the setting is made on site with the operating pressure of the station.
Applications
ITS de Venezuela
ITS quotes new Fisher OSE and VS100 devices, regulators with integrated slam-shut and their genuine parts (trip springs, diaphragms, plugs, gaskets and mechanisms), and services installed ones: mechanism inspection, bench testing and trip point adjustment in the Puerto Ordaz workshop, and verification of trip and reset in the field, with the support of the Venezuela ↔ Orlando inventory. To get a quotation, send this data: gas, maximum inlet pressure, downstream operating pressure, maximum and minimum trip points, flow, line size and connections, and the model of the regulator it will work with; or the model and serial number from the nameplate.
Quote parts or repairMaintenance of pressure regulators and relief devices.
Valve condition assessment before deciding to repair or replace.
On-site support, shutdowns, commissioning and start-up.
Resources
The full category, the technical library and the manufacturer’s official documentation.
Category
Pressure-reducing, backpressure, fuel gas and slam-shut.
Technical library
Our own documents and official Fisher links for each family.
Manufacturer
Product pages, bulletins and manuals on emerson.com.
Both protect against overpressure, but in different ways. Relief discharges gas to limit pressure and keeps supply running; the slam-shut closes the line and avoids discharge to atmosphere, at the cost of interrupting service. Many stations combine the two: a small relief for transient excess and a slam-shut for regulator failure.
Because a trip signals an abnormal condition: a regulator that failed open, a downstream break or a loss of feed. If the valve reopened on its own, it would repressurize a system in failure. Manual reset makes a person inspect the station, correct the cause and restore supply in a controlled way.
Regulators

They hold downstream pressure constant with a diaphragm and a spring: the simple, fast solution for steam, water, air, gases and chemicals.

A pilot amplifies every slight change in outlet pressure and drives the main valve: more capacity and pressure closer to set point than direct operation.

They control upstream pressure: they stay closed up to set point and pass only the excess to the return line, another pressure level or the vent.

They open and close gas to the main burner with a tunable opening speed, so that ignition is correct on field heaters and treaters.

They reduce steam pressure from the distribution lines to the level each consumer needs, on wet or dry steam and without instrument air.
Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.