Gas regulating station with regulators and slam-shut devices

Regulators · Fisher

Fisher slam-shut safety shutoff devices

Overpressure protection by containment: instead of venting gas, the device closes the line and keeps it closed until someone corrects the cause and resets it.

What is a slam-shut device?

A slam-shut valve, or safety shutoff valve, rapidly and totally shuts off gas flow in case of failure, to prevent exceeding the maximum allowable operating pressure downstream of the regulator.

It protects by containment: it closes the line instead of discharging to atmosphere, and most trip on both overpressure and underpressure. It comes standalone, such as the Fisher OSE and VS100, or integrated in regulators of the EZR, EZH, 627 and 299H series.

Gas regulating station with regulators and slam-shut devices
  • Total, rapid shutoff of gas flow
  • Trips on overpressure and underpressure
  • OSE: accuracy up to ±1%
  • Manual reset after tripping

Models

Fisher slam-shut models

Manufacturer reference models for this type. Tell us the exact model or attach the nameplate: scope and availability are confirmed with each quotation.

Brand reference models per the manufacturer’s catalog. ITS quotes new valves and genuine parts to order; it does not publish stock or prices.

How it works

How it works

A trip mechanism senses downstream pressure through an impulse line and compares it with two springs, one for maximum and one for minimum. While pressure is inside the window, a latch holds the plug open against a closing spring. When pressure leaves the limits, the latch releases and the plug slams shut on its seat.

After tripping, the valve does not reopen on its own. For the OSE, the manufacturer states that it stays closed until the system is shut down and the valve is manually reset, and that an O-ring on the plug provides tight shutoff. Its two-stage tripping mechanism reduces nuisance trips caused by vibration or inlet pressure variations.

Constructions and trim

  • Standalone OSE

    Top entry for maintenance without removing the body from the line, accuracy up to ±1% regardless of inlet pressure and flow rate, and an optional limit switch for remote alarm.

  • VS100 family

    VS110 with the VSX4 device and VS120 with the VSX8. Modular body that allows a regulator module to be added later without piping changes.

  • Integrated slam-shut

    The shutoff device is mounted on the regulator itself, as on the EZROSX or the 299HV: regulation and protection by containment in a single unit.

  • Trip on maximum, minimum or both

    The springs of the mechanism define the trip points; the setting is made on site with the operating pressure of the station.

Applications

Where they are used

  • Natural gas regulating and metering stations, upstream of the regulator
  • Fuel gas supply to industrial boilers, furnaces and burners
  • Distribution networks and industrial and commercial service lines
  • Gas feed to turbines and power generation plants
  • Installations where venting gas to atmosphere is not allowed

Why it is chosen

  • Protects by containment: it does not discharge gas to atmosphere
  • Class VI or better shutoff per ANSI/FCI 70-3, according to the manufacturer
  • Shock and vibration resistant design, intended to avoid nuisance trips
  • Remote monitoring available on the OSE through a limit switch

Worth weighing

  • When it trips it interrupts supply: where continuity is critical it is combined with a monitor regulator or with parallel trains
  • Reset is manual and requires someone on site; the cause of the trip must be identified and corrected before resetting

ITS de Venezuela

What ITS does with slam-shut devices

ITS quotes new Fisher OSE and VS100 devices, regulators with integrated slam-shut and their genuine parts (trip springs, diaphragms, plugs, gaskets and mechanisms), and services installed ones: mechanism inspection, bench testing and trip point adjustment in the Puerto Ordaz workshop, and verification of trip and reset in the field, with the support of the Venezuela ↔ Orlando inventory. To get a quotation, send this data: gas, maximum inlet pressure, downstream operating pressure, maximum and minimum trip points, flow, line size and connections, and the model of the regulator it will work with; or the model and serial number from the nameplate.

Quote parts or repair

Resources

Resources

The full category, the technical library and the manufacturer’s official documentation.

FAQ

Frequently asked questions

All frequently asked questions
Slam-shut or relief valve?

Both protect against overpressure, but in different ways. Relief discharges gas to limit pressure and keeps supply running; the slam-shut closes the line and avoids discharge to atmosphere, at the cost of interrupting service. Many stations combine the two: a small relief for transient excess and a slam-shut for regulator failure.

Why is reset manual?

Because a trip signals an abnormal condition: a regulator that failed open, a downstream break or a loss of feed. If the valve reopened on its own, it would repressurize a system in failure. Manual reset makes a person inspect the station, correct the cause and restore supply in a controlled way.

Regulators

More regulators families

Pressure reducing regulators

They hold downstream pressure constant with a diaphragm and a spring: the simple, fast solution for steam, water, air, gases and chemicals.

Pilot-operated regulators for natural gas

A pilot amplifies every slight change in outlet pressure and drives the main valve: more capacity and pressure closer to set point than direct operation.

Back pressure regulators and relief

They control upstream pressure: they stay closed up to set point and pass only the excess to the return line, another pressure level or the vent.

Fuel gas valves

They open and close gas to the main burner with a tunable opening speed, so that ignition is correct on field heaters and treaters.

Steam regulators

They reduce steam pressure from the distribution lines to the level each consumer needs, on wet or dry steam and without instrument air.

Fisher OEM Parts is the online catalog of ACD America Corp., our parent company. It opens in a new tab.

Need slam-shut safety shutoff devices, or repair for yours?

Send the model, the part number or the process data. We reply with availability, lead time and delivery terms.

Product bulletin

Loading the bulletin…

  1. 1Details
  2. 2Verification
  3. 3Request

Message us on WhatsApp

We verify your details and connect you with the specialist for your region.

Receive the phone code by

We will send one code to your email and another to your phone.